Ce Approval Fixed Ash3 Gas Leak Detector Without Display
Reference FOB Price: | US $100.00-180.00 / Piece |
---|---|
Min. Order: | 2 Pieces |
Brand: | Ae |
---|---|
Customized: | Customized |
Portable: | Non Portable |
Certification: | FCC, CE, ISO |
Gas: | Combustible Gas, Methane, CH4 |
Type: | Catalytic Combustion |
Basic Info
Model NO.
AG200
Gas Sensor
Advanced Sensor Made in UK
Detection Principle
Electrochemical & Infrared & Pid
Protection Grade
IP65
Explosion-Proof Grade
Ex Diict6
Sensor Life
2~3years for Electrochemical
Output Signal
4-20mA
Working Voltage
15~30VDC
Environment Temperature
-10c~50c
Display
OLED Display
Transition Cable
Rvvp 3*1.5m M2
Transport Package
Carton
Specification
235*175*135mm
Trademark
AE
Origin
Nanjing, China
HS Code
8531100000
Production Capacity
10000/Month
Product Description
CE approval fixed ASH3 gas leak detector without display
Introduction
China Manufacturer Combustible Gas Leak Detector with UK City Sensor is a classic product of AIYI Technologies, which is suitable for most areas where it is necessary to detect flammable gas, oxygen, and toxic gas. The product responds quickly with an advanced gas sensor; ingress protection to IP65.
China Manufacturer Combustible Gas Leak Detector with UK City Sensor is a classic product of AIYI Technologies, which is suitable for most areas where it is necessary to detect flammable gas, oxygen, and toxic gas. The product responds quickly with an advanced gas sensor; ingress protection to IP65.
Features
-Advanced gas sensors, fast response with a long lifespan, safer and more reliable.
-IP65 design with body material in stainless steel and aluminum alloy, suitable for harsh environments.
-4-20mA/Rs485 signal output that can upload the signal to the control panel.
-Built-in relay and compatible with sound light alarm
-Complete product certification (ATEX, SIL, CCCF, etc.)
Specifications
Description | Specifications | Anr-N | Anr-S | AG200 |
Gas Detected | ||||
Ex | catalytic combustion | √ | √ | - |
toxic | electrochemical | - | - | √ |
Function | ||||
measure range | see QUICK-SELECTION-TABLE | √ | √ | √ |
response time* | T90≤30S | √ | √ | - |
T90≤60/180S | - | - | √ | |
accuracy* | ≤±5%F.S | √ | √ | √ |
repeatability* | ≤2%F.S | √ | √ | √ |
Electric | ||||
power supply | 18-28VDC(standard 24VDC) | √ | √ | √ |
power consumption | ≤2.5W | √ | √ | - |
≤1.5W | - | - | √ | |
signal output | 4-20mA | √ | - | √ |
RS485 | - | √ | √ | |
wiring | three-wire | √ | - | √ |
four-wire | - | √ | √ | |
suitable cable | RVVP3*1.5mm2 | √ | - | √ |
RVVP4*1.0mm2 | - | √ | √ | |
relay output | 1 passive relay (250VAC/5A 30VDC/5A) | √ | √ | √ |
Display | ||||
OLED screen | N/A | √ | √ | √ |
Environment | ||||
ingress protection | IP65 | √ | √ | √ |
operating temperature | -40ºC~70ºC | √ | √ | - |
-20ºC~60ºC | - | - | √ | |
operating humidity | 10~95%RH non-condensing | √ | √ | √ |
operating pressure | 80-120kPa | √ | √ | √ |
Structure | ||||
body material | ADC12 aluminum alloy +316L stainless steel | √ | √ | √ |
close nipple | NPT1/2 | √ | √ | √ |
weight | about 1.3kg | √ | √ | √ |
dimensions | 165*140*78mm(H*W*D) | √ | √ | √ |
Certificates | ||||
CPA | 2009C170-32 | √ | √ | √ |
EX | ExdIICT6 Gb | √ | √ | √ |
CCCF | 073184850117ROM | √ | - | - |
073184850119ROM | - | √ | - | |
SIL | SIL2 | √ | √ | √ |
ATEX | ExdbIICT6 Gb | √ | √ | √ |
Note:* refers to there's some difference vary from different gas, please contact the manufacturer for details. |