| Customization: | Available |
|---|---|
| Brand: | Ae |
| Customized: | Customized |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Description | Specifications | AF110 | AF111 | AG310 | AG311 |
| Gas Detected | |||||
| Ex | Catalytic combustion | √ | √ | - | - |
| Toxic | Electrochemical | - | - | √ | √ |
| Function | |||||
| Measure range | See QUICK-SELECTION-TABLE | √ | √ | √ | √ |
| Response time* | T90≤30S | √ | √ | - | - |
| T90≤60/180S | - | - | √ | √ | |
| Accuracy* | ≤±5%F. S | √ | √ | √ | √ |
| Repeatability* | ≤2%F. S | √ | √ | √ | √ |
| Electric | |||||
| Power supply | 18-28VDC(standard 24VDC) | √ | √ | √ | √ |
| Power consumption | ≤3W | √ | √ | - | - |
| ≤2W | - | - | √ | √ | |
| Signal output | 4-20mA | √ | - | √ | - |
| RS485 | - | √ | - | √ | |
| Wiring | Three-wire | √ | - | √ | - |
| Four-wire | - | √ | - | √ | |
| Suitable cable | RVVP3*1.5mm2 | √ | - | √ | - |
| RVVP4*1.0mm2 | - | √ | - | √ | |
| Relay output | 2 passive relay (250VAC/5A 30VDC/5A) | √ | √ | √ | √ |
| Display & Operation | |||||
| Display | OLED display | √ | √ | √ | √ |
| Indicator light | Power, fault, alarm-1, alarm-2 | √ | √ | √ | √ |
| Operation method | Remote control operation | √ | √ | √ | √ |
| Environment | |||||
| Ingress protection | IP66 | √ | √ | √ | √ |
| Operating temperature | -40ºC~70ºC | √ | √ | - | - |
| -20ºC~60ºC | - | - | √ | √ | |
| Operating humidity | 10~95%RH non-condensing | √ | √ | √ | √ |
| Operating pressure | 80-120kPa | √ | √ | √ | √ |
| Structure | |||||
| Body material | ADC12 aluminum alloy +316L stainless steel |
√ | √ | √ | √ |
| Close nipple | NPT1/2 | √ | √ | √ | √ |
| Weight | About 2.3kg | √ | √ | √ | √ |
| Dimensions | 184*220*99mm(H*W*D) | √ | √ | √ | √ |
| Certificates | |||||
| CPA | 2015C563-32 | √ | √ | √ | √ |
| EX | ExdibIICT6 GB | √ | √ | √ | √ |
| CCCF | 073184850122ROM | √ | - | - | - |
| 073184850123ROM | - | √ | - | - | |
| SIL | SIL2 | √ | √ | √ | √ |
| ATEX | ExdbiIICT6 GB | √ | √ | √ | √ |
| Note: * refers to there's some difference vary from different gas, please contact the manufacturer for details. | |||||